Product Description:
The DPA 503N & AIF 503N are fully compatible three-phase harmonics and flicker analyzers manufactured by EMTEST in Switzerland. The DPA 503N is a fully compliant analyzer that is fully compatible with the latest IEC/EN 61000-3-2 and -12, IEC/EN 61000-3-3 and -11, and JIS 61000-3-2 and -12. It follows the design specifications of IEC/EN 61000-4-7 (for Class I instruments) and IEC/EN 61000-4-15. It follows the design specifications of IEC/EN 61000-4-7 (for Class I instruments) and IEC/EN 61000-4-15.
It forms a complete harmonic and flicker measurement system together with the three-phase flicker impedance AIF 503N (options 16, 32, 63 or 75 A), which includes the reference impedance Zref (IEC 61000-3-3) and the test impedance Ztest (IEC 61000-3-11). By adding the VLCM option, the measurement range can be extended to the mA range (single phase) to measure low power EUTs such as LEDs.
DPA 503N Product Features:
- Compact Harmonic and Flicker System
- Digital power analyzer/flicker meter in accordance with IEC standards.
- Integrated switchable flicker impedance Zref and Ztest
- Wide harmonic measurement range
- IEC 61000-3-2 / -12 Harmonics
- IEC 61000-3-3 / -11 Software for comprehensive flicker analysis and reporting
DPA 503N & AIF 503N Technical Data:
DPA 503N Technical Data:
<<<<提醒:左右滑动表格>>>>Harmonic Flicker Test System Model | DPA 503N |
Product name | Three-phase harmonic analyzer and scintillation analyzer |
branding | AMETEK-EMTEST |
agent | EUTTEST |
usable phase | three-phase power supply |
voltage | 3 channels (L1, L2, L3) 10 - 530 Vrms (4 kVpeak), 16 bit, 15 - 3000 Hz Accuracy: ± 0.04 % range ± 0.30 % reading |
amps | 3 channels (L1, L2, L3) Internal: 0 - 16 / 32 / 63 or 75 A rms (depending on AIF 503 N model) External: depending on the current transformer used euttest Accuracy: ± 0.1 % Range ± 0.70 % Reading ± 0.08 % (Frequency/1000) |
Harmonic Analyzer Mode Conformity | Conforms to IEC 61000-4-7 version 1 and applies to IEC 61000-3-2 version 2.1, IEC 61000-3-12 (with external current transformer), JIS 61000-3-2 and related standards. |
Functions of Harmonic Analyzer | 1st harmonic to 50th harmonic, rectangular measurement window (8, 10, 12, or 16 cycles), 16-bit ADC, anti-alias filter (> 90 dB), FFT algorithm, smoothing filter (1x 1.5 sec digital low-pass filter, on/off selectable), grouping (on/off), PLL synchronization |
Flicker Analyzer Mode Compliance | euttest IEC 61000-3-3, IEC 61000-3-11 and related standards according to IEC 61000-4-15 (120 / 230 V, 50 / 60 Hz) Accuracy: better than 5% (according to IEC 61000-4-15) Observation time: Pst min. 1 minute, optional |
Scintillation Analyzer Measurable Parameters | Pst, Plt, Vrms, dc, dt, dmax, Tmax, P50%S, P10%S, P3%S, P1%S, P0.1% |
test software | Compliance Test Studio 23 (CTS 23) see details below |
Other Recommended Products | If you only need to test the EUT for single phase power: Please purchase EUTTEST's products.DPA 500N maybe DPA 500N1.1 Harmonic scintillation analyzer metrology equipment HFG01KIT01 |
External flicker impedance AIF 503N Technical Data:
<<<<提醒:左右滑动表格>>>>AIF 503N16.4 | AIF 503N32.4 | AIF 503N63.4 | AIF 503N75.4 | |
current range | 1 - 16 A | 1 - 32 A | 1 - 63 A | 1 - 75 A |
voltage | 3 x 400V ±10% | |||
frequency | 47 - 63 Hz | |||
Zref | Including, according to IEC 60725, non-neutral 0.24 Ω + j0.15 Ω and neutral 0.16 Ω + j0.10 Ω. | |||
Ztest | Depending on the configuration chosen by the customer, contact euttest for more information. |
Test software Compliance Test Studio 23 (CTS 23):

Test Software Compliance Test Studio 23 (CTS 23)
The EMTEST Compliance Test Studio 23 (CTS 23) is the software tool required to operate a harmonic and scintillation analysis system. It has all the functions for controlling DPA 503N and AIF 503N, uploading recorded measurement data, and classifying and analyzing them. It includes analyses according to the latest standards, as well as procedures that follow the requirements of previous standards. Simple fault/passage functions enable quick analysis, while detailed data can be used for extended analysis and EUT evaluation.The CTS 23 has a powerful documentation function with direct export to Word, PDF and other file formats.
EMTEST CTS 23 Software Testing Functions:
<<<<提醒:左右滑动表格>>>>software functionality | Conformity Standard No. |
Harmonic test function | IEC 61000-3-2 Revisions 3.2, 4, 5, 5.1 and 5.2 IEC 61000-3-12 Revisions 1, 2 and 2.1 JIS C 61000-3-2 2005 and 2019 editions EN 12015 2014 IEC 61000-3-16 1st Edition ECE R10 5th and 6th editions Ecodesign LED (CELEX 2019/2020) Various manufacturer standards |
Flicker test function | IEC 61000-3-3 Revisions 1.2, 2, 3 and 3.2 IEC 61000-3-11 1st and 2nd editions DIN EN 61000-3-3 euttest ECE R10 5th and 6th editions Various manufacturer standards |
specificities | Standards library with pre-programmed settings, gapless logging for post-processing analysis and changing standards/classifications, PASS/FAIL evaluation, test report generator (customizable), advanced analysis with access to detailed test data |
AIF 503N16.3 and 16.5 Independent Flicker Impedance
AIF 503N16.3 and 16.5 - Independent three-phase flicker impedance 16 A
The AIF 503N16.3 and AIF 503N16.5 are self-contained three-phase flicker impedances up to 16 A per line, including a reference impedance, Zref, according to IEC 60725. In combination with the DPA 503N three-phase harmonics and flicker analyzer and power supply (ACS 503N or NetWave), they perform flicker tests according to IEC 61000-3-3, IEC 61000-3-11 (16 A maximum) and similar standards. IEC 61000-3-3, IEC 61000-3-11 (up to 16 A) and similar standards. Its compact design makes it the ideal impedance for small harmonic and flicker setups.
Three parallel outputs allow easy connection of the EUT: CEE-16 connector, three standard power sockets (country-specific) and laboratory connector (4 mm). Harmonic emission measurements can bypass the internal impedance. The AIF 503N16.3 bypass switch is controlled by the DPA 503N. The AIF 503N16.5 bypass switch is manually controlled by a rotary switch on the front.